| Price | RM15,302.00 |
| Product SKU | 1623-KIT |
| Brand | Fluke |
| Availability | In Stock |
| Shipping Fee | |
| Quantity |
|
Description
Highlight
- One-button measurement concept
- 3- and 4-pole earth ground measurement
- 4-pole soil resistivity testing
- Selective testing, no disconnection of ground conductor (1 clamp)
- Stakeless testing, quick ground loop testing (2 clamps)
- Measuring frequency 128 Hz
Fluke 1623-KIT Basic Geo Earth Ground Tester
- One-button measurement concept
- 3- and 4-pole earth ground measurement
- 4-pole soil resistivity testing
- Selective testing, no disconnection of ground conductor (1 clamp)
- Stakeless testing, quick ground loop testing (2 clamps)
- Measuring frequency 128 Hz
| RA 3-pole Ground Resistance Measurement (IEC 1557-5) | |
| Measuring voltage | Vm = 48 V ac |
| Short circuit current | > 50 mA |
| Measure frequency | 128 Hz |
| Resolution | 0.001 Ω to 10 Ω |
| Measuring range | 0.001 Ω to 19.99 kΩ |
| Intrinsic error | ± (2 % of reading + 3 digit) |
| Operating error | ± (5 % of reading + 3 d) |
| RA 4-pole Ground Resistance Measurement (IEC 1557-5) | |
| Measuring voltage | Vm = 48 V ac |
| Short circuit current | > 50 mA |
| Measure frequency | 128 Hz |
| Resolution | 0.001 Ω to 10 Ω |
| Measuring range | 0.001 Ω to 19.99 kΩ |
| Intrinsic error | ± (2 % of reading + 3 d) |
| Operating error | ± (5 % of reading + 3 d) |
| RA 3-pole Ground Resistance Measurement With Current Clamp | |
| Measuring voltage | Vm = 48 V ac |
| Short circuit current | > 50 mA |
| Measure frequency | 128 Hz |
| rResolution | 0.001 Ω to 10 Ω |
| Measuring range | 0.001 Ω to 19.99 kΩ |
| Intrinsic error | ± (7 % of reading + 3 d) |
| Operating error | ± (10 % of reading + 5 d) |
| RA 4-pole Selective Ground Resistance Measurement With Current Clamp | |
| Measuring voltage | Vm = 48 V ac |
| Short circuit current | > 50 mA |
| Measure frequency | 128 Hz |
| Resolution | 0.001 Ω to 10 Ω |
| Measuring range | 0.001 Ω to 19.99 kΩ |
| Intrinsic error | ± (7 % of reading + 3 d) |
| Operating error | ± (10 % of reading + 5 d) |
| Stakeless Ground Loop Measurement | |
| Measuring voltage | Vm = 48 V ac |
| Measure frequency | 128 Hz (125 Hz on request) |
| Noise current (Iext) | Max. Iext = 10 A (ac) (RA < 20 Ω) |
|
Max. Iext = 2 A (ac) (RA < 20 Ω) |
|
| Resolution | 0.001 Ω to 0.1 Ω |
| Measuring range | 0.001 Ω to 199.9 kΩ |
| Intrinsic error | ± (7 % of reading + 3 d) |
| Operating Error | ± (10 % of reading + 5 d) |
| Environmental Specifications | |
| Working temperature | -10 °C to +50 °C |
| Operating temperature | 0 °C to +35 °C |
| Nominal temperature | +18 °C to +28 °C |
| Storage temperature | -20 °C to +60 °C |
| Climatic class | C1 (IEC 654-1), -5 °C to + 45 °C, 5 % to 95 % RH |
| Protection type | IP56 for case, IP40 for battery door according to EN 60529 |
| Safety Specifications | |
| Safety rating | CAT II, 300 V |
| Mechanical And General Specifications | |
| Display | 1999 digit LCD – display with special symbols, digit height 25 mm, fluorescent backlight |
| Size | 133 mm x 187 mm x 250 mm |
| Weight | 1.1 kg (including batteries) |
| Warranty | Two years |
| Battery life | Typical > 3000 measurements |
Fluke 1623 Kit - Basic Geo Earth Ground Tester
Basic Geo Earth Ground Tester
Includes:
- Fluke 1623 tester
- 2 test leads
- 4 earth ground stakes
- 3 cable reels with wire (2-25 m, 1-50 m)
- 2 clamps (one inducing, one sensing)
- Batteries
- User's manual
- Rugged carrying case
Reviews (0)
view all
back
LatestMore
RM42.00
RM790.00
RM26.00
RM0.00
RM0.00
RM390.00
RM9,000.00
RM595.00
RM195.00
RM2,550.00
RM3,800.00
RM3,500.00
RM1,800.00
RM395.00
FeaturedMore
RM135.00
RM4,200.00
RM43.00
RM65.00
RM1,600.00
RM3,600.00
RM1,495.00
RM504.00
RM608.00
RM920.00
RM6,800.00
RM6,900.00
RM7,900.00
RM18,500.00
RM1,580.00
RM3,675.00
RM2,800.00